	The EN-Ⅱ compact busduct system, in conformity to GB7251 and IEC61439, with rated operating voltage of 690V, rated insulated voltage of 1000V, operating frequency of 50-60 Hz, rated operating current of 250-6300A, maximum tapping current of 1600A, and level of protection IP42&IP54 (up to IP66), is applicable to the following power supply and distribution system: three-phase three-wire, three-phase four-wire and three-phase five-wire, etc. In addition, the configuration of multiple conductor specification is provided, such as standard cooper conductor, 100%-200% neutral line and aluminum conductor, etc., to meet customers’ requirements for different application scenarios.  
 
	
                    
	
 
	
 
	 
		
			
				| 
						Standard 
					 | 
						IEC61439-6、GB7251.6 
					 |  
				| 
						Certificate 
					 | 
						CCC 
					 |  
				| 
						System 
					 | 
						Three-phase three-wire, three-phase four-wire, three-phase five-wire,and three-phase five-wire(enclosure as PE) 
					 |  
				| 
						Ambient temperature 
					 | 
						Not exceeding +40℃,not exceeding +35℃ on average in 24 hours 
					 |  
				| 
						Level of protection 
					 | 
						Up to IP54 for the plug-in busway system,up to IP66 for the feeder busway system 
					 |  
				| 
						Tightening torque of connector(Nm) 
					 | 
						68±7 
					 |  
				| 
						Conductor material  
					 | 
						Cooper busbar with Tin plated, aluminum busbar with cooper and tin plated 
					 |  
				| 
						Color of busway system 
					 | 
						Electrostatic powder sprayed,RAL7035(light gray) 
					 |  
				| 
						Tap-off point configuration  
					 | 
						1-10 ports can be set on the front and reverse side for the standard straight line section with the length of 3 meters 
					 |  
				| 
						Rated isolating voltage Ui AC(V) 
					 | 
						1000 
					 |  
				| 
						Rated operating voltage Ue AC(V) 
					 | 
						380~690 
					 |  
				| 
						Rated frequency f(Hz) 
					 | 
						50/60 
					 |  
				| 
						Busway system current(A) 
					 | 
						250~6300 
					 |  
				| 
						Tap-off unit current(A) 
					 | 
						From 16A,up to 1600A 
					 |  
				| 
						Voltage class/pollution class 
					 | 
						Ⅲ/3 
					 | 
                    
	
 
	
 
	static/file/20180622225341694169 
 
	  
 
	
 
 
	
                    
                     |